6200 ION |
7300 ION |
7330 ION |
7350
ION |
7500 ION |
7600 ION |
7700
ION |
8300
ION |
8400
ION |
8500
ION |
POWER,
ENERGY, & DEMAND |
|
|
|
|
|
|
|
|
|
|
Voltage/current: per phase, average, unbalance |
|
|
|
|
|
|
|
|
|
|
Power: real, reactive, apparent, power factor, frequency |
|
|
|
|
|
|
|
|
|
|
Energy: bi-directional, total, import, export, net |
|
|
|
|
|
|
|
|
|
|
Demand: block, sliding window, thermal, predicted |
|
|
|
|
|
|
|
|
|
|
POWER
QUALITY ANALYSIS |
6200
ION |
7300 ION |
7330 ION |
7350
ION |
7500 ION |
7600 ION |
7700
ION |
8300
ION |
8400
ION |
8500
ION |
Sag/swell monitoring |
|
|
|
|
|
|
|
|
|
|
Symmetrical components: zero, -'ve, +'ve |
|
|
|
|
|
|
|
|
|
|
Transient detection, microseconds |
|
|
|
|
|
65 |
130 |
|
|
65 |
Harmonics (ind., even, odd, total) |
THD |
15th |
15th |
31st |
63rd |
63rd |
63rd |
31st |
63rd |
63rd |
Sampling rate, max samples/cycle |
64 |
32 |
32 |
64 |
128 |
256 |
128 |
64 |
128 |
256 |
Flicker (IEC 61000-4-7/4-15) |
|
|
|
|
|
|
|
|
|
|
EN50160 |
|
|
|
|
|
|
|
|
|
|
Configurable for IEEE 519-1992, IEEE 1159, SEMI |
|
|
|
|
|
|
|
|
|
|
Reliability/uptime
expressed as # of 9's |
|
|
|
|
|
|
|
|
|
|
DATA
& WAVEFORM LOGS |
6200
ION |
7300 ION |
7330 ION |
7350
ION |
7500 ION |
7600 ION |
7700
ION |
8300
ION |
8400
ION |
8500
ION |
Triggered by setpoint, schedule, or external signal |
|
|
|
|
|
|
|
|
|
|
SOE logs, variable log depth |
|
|
|
|
|
|
|
|
|
|
Min/max logs for any parameter |
|
|
|
|
|
|
|
|
|
|
Historical logs, max # of channels |
|
|
32 |
96 |
320 |
640 |
320 |
32 |
160 |
320 |
Waveform logs, max # of cycles |
|
|
|
48 |
96 |
96 |
96 |
|
|
96 |
Timestamps, resolution in seconds |
|
|
0.001 |
0.001 |
0.001 |
0.001 |
0.001 |
0.001 |
0.001 |
0.001 |
GPS time synchronization |
|
|
|
|
|
|
|
|
|
|
COMM
PORTS & I/O (max #) |
6200
ION |
7300 ION |
7330 ION |
7350
ION |
7500 ION |
7600 ION |
7700
ION |
8300
ION |
8400
ION |
8500
ION |
RS-232/485 ports |
|
|
|
|
1 |
1 |
1 |
1 |
1 |
1 |
RS-485-only ports |
1 |
1 |
2 |
2 |
1 |
1 |
2 |
1 |
1 |
1 |
Ethernet ports |
|
1 |
1 |
1 |
1 |
1 |
1 |
|
1 |
1 |
Infrared optical ports |
|
1 |
1 |
1 |
1 |
1 |
|
1 |
1 |
1 |
LonWorks ports (LonTalk support) |
|
1 |
|
|
|
|
|
|
|
|
PROFIBUS ports |
|
1 |
|
|
|
|
|
|
|
|
Built-in modem: |
|
|
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Modbus RTU Slave on serial, Ethernet, modem, infrared ports |
|
|
|
|
|
|
|
|
|
|
Modbus
TCP on Ethernet ports |
|
|
|
|
|
|
|
|
|
|
DNP 3.0 on serial, modem, infrared ports |
|
|
|
|
|
|
|
|
|
|
EtherGate™: direct data transfer from Ethernet to RS-485 |
|
|
|
|
|
|
|
|
|
|
ModemGate™: modem access for other meters vai RS-485 |
|
|
|
|
|
|
|
|
|
|
MeterM@il®:
alarm/logged data emailed from meter |
|
|
|
|
|
|
|
|
|
|
Webmeter:
embedded webserver provides data via web pages. |
|
|
|
|
|
|
|
|
|
|
Analog inputs |
|
4 |
4 |
4 |
4 |
4 |
18 |
|
|
|
Analog outputs |
|
4 |
4 |
4 |
4 |
4 |
30 |
4 |
4 |
4 |
Digital status/counter inputs |
|
|
4 |
4 |
8 |
8 |
38 |
8 |
8 |
8 |
Digital relay outputs (control/pulse) |
2 |
4 |
4 |
4 |
7 |
7 |
30 |
8 |
8 |
8 |
SETPOINTS,
ALARMING, & CONTROL |
6200
ION |
7300 ION |
7330 ION |
7350
ION |
7500 ION |
7600 ION |
7700
ION |
8300
ION |
8400
ION |
8500
ION |
Setpoints, min response time |
|
|
1 sec |
1
sec |
½ cycle |
½ cycle |
1 cycle |
1
sec |
½ cycle |
½ cycle |
Math, logic, trig, log, linearization formulas |
|
|
|
|
|
|
|
|
|
|
Single- & multi-condition alarms |
|
|
|
|
|
|
|
|
|
|
Remote alarm notification |
|
|
|
|
|
|
|
|
|
|
REVENUE
METERING |
6200
ION |
7300 ION |
7330 ION |
7350
ION |
7500 ION |
7600 ION |
7700
ION |
8300
ION |
8400
ION |
8500
ION |
ANSI C12.16 accuracy compliant* |
|
|
|
|
|
|
|
|
|
|
ANSI C12.20 0.2 compliant* |
|
|
|
|
|
|
|
|
|
|
IEC 60687 0.2S compliant* |
|
|
|
|
|
|
|
|
|
|
IEC
60687 accuracy class 0.5S compliant |
|
|
|
|
|
|
|
|
|
|
ANSI
class 10 (5A nominal, 10A max) |
|
|
|
|
|
|
|
|
|
|
ANSI
class 2, IEC 1/10 (1A nominal, 10A max) |
|
|
|
|
|
|
|
|
|
|
ANSI
class 20, IEC 5/20 (5A nominal, 20A max) |
|
|
|
|
|
|
|
|
|
|
MV-90 support |
|
|
|
|
|
|
|
|
|
|
Multi-year scheduling: hourly activity profiles |
|
|
|
|
|
|
|
|
|
|
Transformer/line loss compensation |
|
|
|
|
|
|
|
|
|
|
|
6200
ION |
7300 ION |
7330 ION |
7350
ION |
7500 ION |
7600 ION |
7700
ION |
8300
ION |
8400
ION |
8500
ION |
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
* Products meet or exceed
the accuracy requirements of the standards listed. All products tested
internally by Power Measurement. Some products tested by third-party
laboratory. Due to form factor of some meters, not all ANSI/IEC compliance
tests may apply. Contact Power Measurement for further clarification. |